The two bodies every data centre knows

Rack power arrives on pin & sleeve because it locks against pull-out, seals against the floor grille, and cannot be plugged into the wrong voltage. Two families do almost all of it: the 320P6W single-phase feed and the 9h blue five-wire whip.

The facts

PolesHourVoltageBody colour
2P+E (3 wire)4h100-130VYellow
2P+E (3 wire)5h277VGrey
2P+E (3 wire)6h200-250VBlue
2P+E (3 wire)7h480VRed
2P+E (3 wire)8h550V DCBlack
2P+E (3 wire)9h250V DCBlue
PolesHourVoltageBody colour
3P+N+E (5 wire)5h3ØY 347/600VBlack
3P+N+E (5 wire)6h220/380-240/415VRed
3P+N+E (5 wire)7h3ØY 277/480VRed
3P+N+E (5 wire)9h3ØY 120/208VBlue

320P6W: the 20 A single-phase feed

Two poles and earth, 200–250 V, 20 A North American / 16 A IEC, IP67. It is the plug on the cord that runs from an overhead busway tap or a wall receptacle to a rack PDU whose inlet is a C20 or C14, and on cords that go straight to a server's C19 or C13. We list these cords today in the 6h cell: 320P6W to C13, C15, C19 and C21, including the A-Lock connectors that hold in the equipment, and to NEMA 6-15R, 6-20R, L6-15R, L6-20R and L6-30R.

9h blue on five wires: the North American three-phase whip

3ØY 120/208 V is the rack distribution voltage in most North American data centres: three phases at 120 V to neutral, 208 V between phases. On a five-wire body that is 9h, blue. A 30 A rack PDU takes a 530P9W; a 60 A one a 560P9W. These whips are built to order and the clock says so on those cells; ask and we quote with lead time.

9h blue on four wires: 208 V delta

Where the PDU needs only line-to-line 208 V, the neutral goes away and the body is four wire: 430P9W or 460P9W. Same hour, same colour, one fewer sleeve.

Abroad: 6h red 3P+N+E

A 230/400 V rack in Europe or Asia takes the 6h red five-wire body at 16 or 32 A (the 20 and 30 A cells on our clock). The cable behind it is H07RN-F or a harmonised PVC cord to the local rules.

Why not a locking NEMA plug

An L6-30P locks too, but it does not stop you plugging 208 V into a 120 V PDU, and it does not seal. Pin & sleeve does both, which is why the busway makers standardised on it.